Modbus

Modbus is a communication protocol widely used for connecting industrial electronic devices. The following instructions outline the primary functions available for establishing communication between a Modbus master and slave devices, along with details on how to read from and write to various types of Modbus registers.

Instruction List

The following table provides an overview of Modbus functions used for communication:

CommandFunction
ModbusCreateCreate a Modbus master and establish a connection with a slave.
ModbusRTUCreateCreate a Modbus master based on RS485 interface.
ModbusCloseDisconnect from the Modbus slave.
GetInBitsRead contact registers.
GetInRegsRead input registers.
GetCoilsRead coil registers.
SetCoilsWrite to coil registers.
GetHoldRegsRead holding registers.
SetHoldRegsWrite to holding registers.

The Modbus function codes for various register types are as follows:

Register TypeRead RegisterWrite Single RegisterWrite Multiple Registers
Coil Register01050F
Contact Register02--
Input Register04--
Holding Register030610

ModbusCreate

Prototype

ModbusCreate(IP, port, slave_id, isRTU)

Description

This function creates a Modbus master and establishes a connection with a slave device. It supports a maximum of 15 simultaneous connections.

  • For built-in slave devices, set IP to the robot's IP (default is 192.168.5.1, which can be modified) and the port to 502 (map1) or 1502 (map2). Refer to the Modbus register definition appendix for details.
  • For third-party slave devices, set IP and port to the respective addresses.

Required Parameters

  • IP: Slave device's IP address.
  • port: Slave device's port.

Optional Parameters

  • slave_id: Slave ID.
  • isRTU: Boolean value. If omitted or set to false, it establishes a Modbus TCP connection; if true, it establishes a Modbus RTU connection.

Note: This parameter determines the protocol format for data transmission after the connection is established and does not affect the connection result. If set incorrectly, the connection may succeed, but subsequent communications may fail.

Return Values

  • err:

    • 0: Successfully created the Modbus master.
    • 1: The maximum number of Modbus masters has been reached; creation failed.
    • 2: Initialization of the master failed (check IP, port, network, etc.).
    • 3: Connection to the slave failed (check if the slave is operational and if the network is functional).
  • id: Returns the index of the created master for subsequent Modbus function calls. Range: [0, 14]

Example

-- Create Modbus master and connect to specified slave.
local ip = "192.168.5.123"
local port = 503
local err = 0
local id = 0
err, id = ModbusCreate(ip, port, 1)

-- Create Modbus master and connect to built-in slave.
local ip = "192.168.5.1"
local port = 502
err, id = ModbusCreate(ip, port)

ModbusRTUCreate

Prototype

ModbusRTUCreate(slave_id, baud, parity, data_bit, stop_bit)

Description

Creates a Modbus master based on RS485 interface and establishes a connection with a slave device. It supports a maximum of 15 simultaneous connections.

Required Parameters

  • slave_id: Slave ID.
  • baud: Baud rate for the RS485 interface.

Optional Parameters

  • parity: Parity bit. "O" for odd, "E" for even, "N" for none. Default is "E" if not provided.
  • data_bit: Data bit length. Default value is 8.
  • stopbit: Stop bit length. Options are 1 or 2. Default value is 1.

Return Values

  • err:
    • 0: Successfully created the Modbus master.
    • 1: Failed to create the Modbus master.
  • id: Returns the index of the created master for subsequent Modbus function calls.

Example

-- Create Modbus master and connect to RS485 slave with ID 1 and baud rate of 115200.
err, id = ModbusRTUCreate(1, 115200)

ModbusClose

Prototype

ModbusClose(id)

Description

Disconnects from the Modbus slave and releases the master.

Required Parameters

  • id: Index of the created master.

Return Values

  • Operation result:
    • 0: Successfully disconnected.
    • 1: Failed to disconnect.

Example

-- Disconnect from the Modbus slave.
ModbusClose(id)

GetInBits

Prototype

GetInBits(id, addr, count)

Description

Reads the values from the Modbus slave's contact register address. Corresponds to Modbus function code 02.

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the contact register.
  • count: Number of continuous contact registers to read (1-2000, depending on the slave's register count and protocol specifications).

Return Values

Returns the values from the contact register address stored in a table. The first value corresponds to the value of the starting address.

Example

-- Read 5 continuous values starting from address 0.
inBits = GetInBits(id, 0, 5)

GetInRegs

Prototype

GetInRegs(id, addr, count, type)

Description

Reads the values from the Modbus slave's input register address based on the specified data type. Corresponds to Modbus function code 04.

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the input register.
  • count: Number of continuous input registers to read (1-125, depending on the slave's register count and protocol specifications).

Optional Parameters

  • type: Data type (default is U16 if omitted).
    • U16: 16-bit unsigned integer (2 bytes, occupying 1 register).
    • U32: 32-bit unsigned integer (4 bytes, occupying 2 registers).
    • F32: 32-bit single-precision float (4 bytes, occupying 2 registers).
    • F64: 64-bit double-precision float (8 bytes, occupying 4 registers).

Return Values

Returns the values from the input register address stored in a table. The first value corresponds to the starting address.

Example

-- Read a 32-bit unsigned integer starting from address 2048.
data = GetInRegs(id, 2048, 2, "U32")

GetCoils

Prototype

GetCoils(id, addr, count)

Description

Reads the values from the Modbus slave's coil register address. Corresponds to Modbus function code 01.

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the coil register.
  • count: Number of continuous coil registers to read (1-2000, depending on the slave's register count and protocol specifications).

Return Values

Returns the values from the coil register address stored in a table. The first value corresponds to the starting address.

Example

-- Read 5 continuous values starting from address 0.
Coils = GetCoils(id, 0, 5)

SetCoils

Prototype

SetCoils(id, addr, count, table)

Description

Writes specified values to the coil registers at the specified addresses. Corresponds to Modbus function codes 05 (write single) and 0F (write multiple).

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the coil register.
  • count: Number of continuous coil registers to write (1-1968, depending on the slave's register count and protocol specifications).
  • table: Values to be written to the coil registers stored in a table. The first value corresponds to the starting address.

Example

-- Write continuous values to 5 coils starting from address 1024.
local Coils = {0, 1, 1, 1, 0}
SetCoils(id, 1024, #Coils, Coils)

GetHoldRegs

Prototype

GetHoldRegs(id, addr, count, type)

Description

Reads the values from the Modbus slave's holding register

address based on the specified data type. Corresponds to Modbus function code 03.

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the holding register.
  • count: Number of continuous holding registers to read (1-125, depending on the slave's register count and protocol specifications).

Optional Parameters

  • type: Data type (default is U16 if omitted).
    • U16: 16-bit unsigned integer (2 bytes, occupying 1 register).
    • U32: 32-bit unsigned integer (4 bytes, occupying 2 registers).
    • F32: 32-bit single-precision float (4 bytes, occupying 2 registers).
    • F64: 64-bit double-precision float (8 bytes, occupying 4 registers).

Return Values

Returns the values from the holding register address stored in a table. The first value corresponds to the starting address.

Example

-- Read a 32-bit unsigned integer starting from address 2048.
holdRegData = GetHoldRegs(id, 2048, 2, "U32")

SetHoldRegs

Prototype

SetHoldRegs(id, addr, count, table)

Description

Writes specified values to the holding registers at the specified addresses. Corresponds to Modbus function codes 06 (write single) and 10 (write multiple).

Required Parameters

  • id: Index of the created master.
  • addr: Starting address of the holding register.
  • count: Number of continuous holding registers to write (1-123, depending on the slave's register count and protocol specifications).
  • table: Values to be written to the holding registers stored in a table. The first value corresponds to the starting address.

Example

-- Write continuous values to 5 holding registers starting from address 2048.
local holdRegs = {100, 200, 300, 400, 500}
SetHoldRegs(id, 2048, #holdRegs, holdRegs)